SHREVEPORT FIRE DEPARTMENT
Fire Prevention Inspection Division
Fire Code Requirements
General Business Occupancies
This checklist provides
some of the basic regulations governing the operation of
General Business
Occupancies. It is not possible to cover
all regulations. If you have questions or concerns, please call or fax the
Shreveport Fire Prevention Division at
(318) 673-6740
or fax (318) 673-6744.
1.
Permits
A. A valid certificate of occupancy from Zoning
is required.
B. Any renovation to the occupancy shall be
authorized by the Building Department and Fire Prevention.
2.
Exits
A. Doors must be unlocked and unblocked when
building is occupied.
B. Required width of an exit or pathways shall
be unobstructed.
C. Exit signs must be illuminated.
D. Panic hardware on exit
doors must operate as designed.
BACK TO TOP
3. Fire
Lanes and Access
A. Properly marked and clear of
obstructions.
B. Limited access control gates installed must
meet requirements of the Gate Code Ordinance.
C. Access Box or Boxes shall be installed in an
accessible location where access to or within a structure or area is difficult
because of security.
4. Fire
Extinguishers
A. Typically, one 2A-10BC extinguisher is
required for every 3,000 sq. ft. of floor space or within 75 ft. of travel
distance. Special hazards may have additional requirements.
B. Fire extinguishers shall be mounted in
conspicuous accessible locations. When mounted, bottom of the extinguisher must
be at least 4 in. from the floor and the top no greater than 5 ft above the
floor. Top shall be no greater than 3.5 ft. if extinguisher weighs more than 40
lbs.
C. Fire extinguishers must be inspected for
proper maintenance annually by a state licensed individual or company.
D. Fire extinguishers shall be recharged or
replace after use by a state licensed individual or company.
5. Fire
Alarm/Detection Systems
A. Approved
fire alarm system shall be installed in accordance to NFPA 72 National Fire
Alarm Code.
B. Systems shall be maintained in an operative
condition at all times, and replaced or repaired when defective by State
licensed individuals. Immediately notify the Shreveport Fire Department at
(673-6740)
if fire alarm system becomes non-operational or is out of service for more than
four (4) hours in a twenty four (24) hour period.
C. Written operating instructions provided and
maintained at an approved location.
D. Manual alarms and smoke alarms shall be
tested at least annually and after modifications by state licensed individuals.
BACK TO TOP
6.
Sprinkler Systems
A. Approved sprinkler systems shall be
installed in accordance to NFPA 13.
B. Systems shall be maintained in approved
working condition and repaired when defective by a State licensed individual.
Immediately notify the Shreveport Fire Department at
(673-6740)
if system become non-operational or is out of service for more than four (4)
hours in a twenty four (24) hour period.
C. Identify controls, drains, and test control
valves with approved signage.
D. Access to valves and/or fire department
connections shall not be obstructed.
E. A sprinkler wrench must be provided. Spare
sprinkler heads of the same types and ratings installed in the building shall
be provided for a system as follows:
1). Less than 300 system heads, a minimum of 6
spare heads.
2). 300 to 1000 system heads, a minimum of 12
spare heads.
3). Over 1,000 system heads, a minimum of 24
spare heads.
F. Maintain an 18-inch clearance between
sprinkler heads and storage.
G. Systems
shall be tested at least annually.
7. Flammable Liquids
A. Post “No Smoking” signs in all areas where
smoking or open flames might be hazardous.
B. Store flammables in approved containers and
must not exceed allowable quantities. Amounts in excess of ten (10) gallons
shall be stored in approved cabinets or rooms.
C. Flammables shall not be stored near exit
doorways, stairways, or other locations that would impede egress.
D. Flammable spray finishes may not be applied
outside of an approved spray booth or room.
BACK TO TOP
8.
Storage
A. Storage shall be maintained 2 ft. or more
from the ceiling in non-sprinkler areas of buildings.
B. Storage is prohibited in boiler rooms,
electrical rooms, mechanical rooms, stairwells, exit ways, and within 10 feet of
incinerators.
C. Outside storage of combustible materials shall not be located within 10 ft. of a property line.
D. Combustible storage in the open shall not exceed 20 ft. in height.
9. Kitchens
A. Fire
extinguishing systems must be installed to protect commercial cooking equipment
that produces grease-laden vapors.
B. If
vent hood has a fire-extinguishing system, one K Class fire extinguisher must be
provided within 30 feet.
C. Fire extinguishing systems must be serviced
at least every 6 months and after activation.
D. Maintain stove and vent hoods free of
grease.
10. Miscellaneous
A. Remove combustible trash daily.
B. Combustible decorations must be flame proof
/frame retardant.
C. Maintain a 24-inch clearance between storage
and ceiling.
D. Provide cover plates for all electrical
panels, outlets, boxes, and junctions.
E. Extension cords shall not be utilized in
place of permanent wiring.
F. Post a correct address visible form the
street. In complexes with multiple buildings, each building must be designated.
G. Secure compressed gas cylinders in an upright
position.
H. Gas-fired appliances must be properly vented
to the outside, have approved flex-type connections, and have cut-off valves.
I. Replace all missing or broken
electrical outlets or switch covers.
J. Keep all fire rated doors closed at all
times.
K. Replace all missing ceiling tiles.
L. Contact Fire Prevention concerning display of
live Christmas Trees within occupancy.